- Copper cabling/components:
- ANSI/TIA-568.2-D (Cat 5e/6/6A/8.1 performance, AXT for 6A), ANSI/TIA-568.0-D (generic)
- ISO/IEC 11801-1 (generic) and -2/-3/-5 as applicable; Classes D/E/EA/FA/I/II
- IEC 61156-x (cable), IEC 60603-7-x (connectors), IEC 60512-99-001/002 (PoE contact endurance)
- IEEE 802.3af/at/bt for PoE
- EN 50173 (EU, if required)
- Fiber cabling/components:
- ANSI/TIA-568.3-D
- ISO/IEC 11801-1 (fiber sections), IEC 61754 (connector interfaces), IEC 61753 (performance)
- IEC 61300-3-35 (endface inspection/cleanliness)
- Pathways, bonding, administration:
- ANSI/TIA-569-D (pathways/spaces)
- ANSI/TIA-607-D (grounding/bonding)
- ANSI/TIA-606-C (labeling/administration)
- ANSI/TIA-942-B (data centers), ANSI/TIA-1005-A (industrial), ANSI/TIA-862-B (BAS), as applicable
- Fire/safety and building code (US):
- NFPA 70 (NEC Articles 725/770/800/840)
- UL 444 (communications cable), UL 1666 (riser), UL 910 (plenum), CMP/CMR/CM/CMG/CMX markings
- UL LP (Limited Power) for high-PoE bundles (optional)
- Field testing/certification (copper):
- Test to selected limit: ANSI/TIA-568.2-D or ISO/IEC 11801 Class
- Field tester compliance: ANSI/TIA-1152-A and IEC 61935-1
- Tester accuracy: Level V (to 1 GHz, Class FA) or Level VI/VI+ (to 2 GHz, Cat 8/Class I/II)
- Permanent Link certification (preferred) or Channel; include NEXT, PSNEXT, ACR-F/PSAACRF, Return Loss, Insertion Loss, Prop Delay, Skew; AXT for Cat 6A+
- Field testing/certification (fiber):
- Tier 1: OLTS per IEC 61280-4-1 (MM) / -4-2 (SM) with reference method; polarity check
- Tier 2: OTDR per IEC 61280-4-5 (as needed)
- Endface pass/fail per IEC 61300-3-35
- Fluke Networks examples:
- Copper: DSX CableAnalyzer series meeting IEC 61935-1 Level V/VI; use Permanent Link adapters
- Fiber: CertiFiber Pro (Tier 1), OptiFiber Pro (Tier 2), FI series for IEC 61300-3-35 inspection
- Deliver certified reports matching TIA/ISO test limits and TIA-606-C labeling.