To connect a servo drive to a PLC or motion controller:
1. Match the control type
Use the drive’s supported interface: pulse/dir, analog ±10V, step/dir, or fieldbus such as EtherCAT, PROFINET, Modbus, CANopen, or Ethernet/IP. Your PLC or motion controller must support the same method.
2. Wire the power safely
Connect the AC or DC input to the drive per its rating. Connect the motor phases U/V/W from the drive to the servo motor. Connect the motor brake, if present, to the proper brake output. Bond all protective earth/ground connections.
3. Connect feedback and safety
If the motor uses an encoder or resolver, connect the feedback cable to the drive, not directly to the PLC. Wire safety inputs such as STO (Safe Torque Off), enable, E-stop, and limit switches as required.
4. Connect command signals
For pulse/dir, wire the controller’s high-speed outputs to the drive command inputs and share common reference/ground as specified. For fieldbus, connect the network cable and set addresses, node IDs, IPs, or station names. For analog control, wire the analog command and analog common.
5. Configure the drive
Set motor parameters, encoder type, command mode, current limits, velocity/position units, and communication settings. Run auto-tuning if available.
6. Program the controller
Create motion commands such as homing, positioning, speed control, or torque control. Map status bits like “ready,” “fault,” “in position,” and “home complete.”
7. Test and commission
Verify wiring, check polarity, jog at low speed, confirm direction, then tune performance. Always follow the drive and controller manuals, as pinouts and parameters vary by manufacturer.