Frequently Asked Questions
How does it measure without touching the flow?
By timing sound through the fluid.
Pulses with the flow arrive sooner than those against it.
That time difference converts to velocity.
Velocity and pipe area give volume.
Nothing is placed in the stream.
There is no restriction to pump against.
What does having no moving parts actually buy?
Stability over a very long service life.
No impeller wears and no bearing seizes.
Mechanical meters drift gradually as they age.
That drift is invisible without recalibration.
It also costs no pumping energy.
Over decades both matter.
When is clamp-on the right choice?
When the system cannot be cut into.
Surveys and temporary measurement suit it.
Retrofit where draining down is impractical.
It installs on a live pipe.
In-line units are more accurate.
Billing generally uses in-line.
What defeats an ultrasonic measurement?
Anything that stops sound crossing cleanly.
Entrained air is the commonest cause.
Heavy aeration or particulate degrades it too.
A poorly vented system produces odd readings.
Vent properly before blaming the meter.
Clamp-on units also need sound pipe wall condition.
Does it still need straight pipe?
Yes, exactly as any flow meter does.
The technology removes the obstruction, not the physics.
A disturbed velocity profile gives a wrong number.
Manufacturers publish upstream and downstream lengths.
Clamp-on installation makes this easy to ignore.
Ignoring it produces confident wrong readings.
What does a clamp-on installation depend on?
Acoustic coupling to the pipe.
Coupling paste or pads transmit the signal.
Surface preparation matters considerably.
Internal scale attenuates the signal.
Pipe material and wall thickness must be entered correctly.
Errors there scale the whole reading.
Can it be used for billing?
In-line certified versions, yes.
Legal metrology approval is required.
Clamp-on is usually not accepted for billing.
Requirements vary by jurisdiction.
Confirm before specifying for charging.
Recertification intervals apply as well.